| Specifications
Power Requirements:
Single phase 120 or 230
Vac ±10%, 50/60 Hz., (fused)
Internal d.c. power supply
± Vdc, 2.4 VA, (fused)
Input Signal:
4 – 20 mAdc; 10 – 50 mAdc;
1 – 5 Vdc and 0 – 10 Vdc; Potentiometer 1000 Ohms.
Impedance, respectively:
249 Ohms; 100 Ohms; 10 kiloOhms;
Other signals are available.
Power Output:
120 Vac at 5.0 A, dual channel
output, isolated from command signal input. All solid state.
Sensitivity:
±0.6% of the total
input signal span for a 30 seconds travel time of the actuator’s shaft.
Dead Band:
0.1 to 10% of the total
signal span.
Zero Adjustment:
50% of span range.
Span Adjustment:
50% of span at low signal
end.
Split Range of Command
Signal:
Built in for up to 50% of
the span by adjusting in the field ZERO and SPAN potentiometers. For example,
the Split Range can be 4 – 12mA or 12 – 20mA.
Ambient Temperatures:
-10°F to 150°F
-40°F to 150°F with
heater
At the Loss of Command
Signal:
The positioner can be set
to drive the actuator to one of the following three fail modes:
1. To maintain the last
position;
2. To be driven in the minimum
signal position;
3. To be driven in the maximum
signal position.
Rotation Indicator:
Red light indicates rotation
toward minimum signal
position. Green light indicates
rotation toward
maximum signal position.
Size:
3.95” x 2.75” x 1.65”